Quick Setup
Navigation bar > > Reports > Templates
The Quick Setup is a guided configuration tool designed to assist users during the initial set up of the EMS system.
It simplifies installation by providing a step-by-step procedure that ensures all essential parameters are correctly defined before the system starts collecting data.
Once the set up is complete, users can access all other sections of the application normally.
Note: the wizard runs automatically when the Web App is accessed for the first time or after a factory reset.
|
Step |
Description |
|---|---|
|
IP Settings |
Defines how the device connects to the network. Users can select DHCP or assign a static IP, and configure gateway, DNS, and hostname parameters. |
| Date & Time |
Sets system time and synchronization mode. Users can select timezone, enable or disable NTP synchronization, and define one or two NTP servers. |
| Measurement settings | Configures the measurement system type (1P, 2P, 3P, 3Pn) and electrical characteristics such as primary current, CT/VT ratio, and measurement direction. |
| Display | In this step, the user defines access credentials for the device display. |
| Preview | Displays a real-time summary of system configuration, showing voltage, current, power, and other measured variables for verification before completing the set up. |
IP Settings
|
Parameter |
Sub-parameter |
Description |
Values |
Default values |
|---|---|---|---|---|
| IP settings |
Hostname |
Name of the device in the network | - | - |
| IP address | Use a DHCP automatic address or a manually inserted one | Get an IP address Automatically (DHCP) | Get an IP address Automatically (DHCP) | |
| Use the following IP Address | ||||
| DNS server address | Use an automatic address or a manually inserted one | Get DNS Server address automatically | Get DNS Server address automatically | |
| Use the following DNS server addresses |
Date & Time
|
Parameter |
Sub-parameter |
Description |
Values |
Default values |
|---|---|---|---|---|
|
Date and time |
EMS date and time |
Current date and time | - | - |
|
Time zone |
Timezone of the device installation | - | - | |
|
Enable NTP |
Activation/deactivation of NTP | - | - |
Measurement settings
|
Parameter |
Sub-parameter |
Description |
Values |
Default values |
|---|---|---|---|---|
| Measure settings | Main Load | Selection of the electrical system | 1P | 3P.N |
| 2P | ||||
| 3P | ||||
| 3P.N | ||||
| Load description | Description of the load selected | - | - | |
| Primary current | Current transformation ratio value |
1-2000 |
1 | |
| CT Ratio |
Primary current value |
10-10000 | 10 | |
| CT orientation | Define the current flow direction | - | - | |
| Measurement mode | Select the measurement mode | Easy connection | Easy connection | |
| Bidirectional type 1 | ||||
| Bidirectional type 2 | ||||
| Digital input function | Define the function of the digital input | Tariff management | Tariff management | |
| Remote | ||||
| Partial meter start/stop | ||||
| Partial meter reset | ||||
| Start-up current for run hour counter (mA) | threshold for run hour meter start in mA | 1-100000 | 1 |
Display
|
Parameter |
Sub-parameter |
Description |
Values |
Default values |
|---|---|---|---|---|
| Display | Security password | Define the password to access the protected information on the display | 1-999999 | 1 |
When the configuration is complete, click Finish. The system saves all parameters and restarts with the new configuration active.
A confirmation message is displayed: Setup completed successfully. The application redirects to Home page.
-
The wizard operates in Wi-Fi 1-to1 (access point) mode during the first set up.
-
Only one client can be connected to the EMS Wi-Fi 1-to-1 (Access Point) during the set up.
-
All steps can be re-accessed later from the Maintenance tab to modify configurations if necessary.
-
If errors occur during saving, the wizard remains open and displays a red warning message specifying the incorrect fields.